RS-485 I/O Modules
4-16
1-ch Thermocouple Input Modules
(with 7-segment LED Display)
1-ch Analog Input Module
1-ch RTD Input Module
Specifications
General
Power Consumption 0.7 W @ 24 V
DC
Support Protocol ASCII command
Analog Input
Channels 1
Input Connections 2, 3, or 4-wire
Input Impedance
2 MΩ
Input Type Pt or Ni RTD
RTD Types and Temperature Ranges
IEC RTD 100 ohms
Pt -100° C to +100° C a = 0.00385
Pt 0° C to +100° C a = 0.00385
Pt 0° C to +200° C a = 0.00385
Pt 0° C to +600° C a = 0.00385
JIS RTD 100 ohms
Pt -100° C to +100° C a = 0.003916
Pt 0° C to +100° C a = 0.003916
Pt 0° C to +200° C a = 0.003916
Pt 0° C to +600° C a = 0.003916
Ni RTD
Ni -80° C to +100° C
Ni 0° C to +100° C
Accuracy ±0.1% or better
Span Drift ±25 ppm/° C
Zero Drift ±3 μV/° C
Specifications
General
Power Consumption 1.2 W @ 24 V
DC
Support Protocol ASCII command
Analog Input
Channels 1
Input Impedance Voltage: 20 MΩ
Current: 125 Ω
(Added by users)
Input Type mV, V or mA
Input Range
±150 mV, ±500 mV, ±1
V, ±5 V, ±10 V and ±20
mA
Accuracy Voltage mode: ±0.1% or
better
Current mode: ±0.2%
or better
Span Drift ±25 ppm/° C
Zero Drift ±6 μV/° C
Digital Input
Channels 1
Logic level 0: +1 V max.
Logic level 1: 3.5 ~ 30 V
pull up current: 0.5 mA,
10 kΩ resistor to +5 V
Event Counter
Max. input freq.: 50 Hz
Min. input pulse width:
1 msec.
Digital Output
Channels 2, open collector to 30
V, 30 mA max. load
Power Dissipation 300 mW
ADAM-4011/4011D
ADAM-4012
ADAM-4013
ADAM-4012 ADAM-4013
Specifications
General
Power Consumption 1.4 W @ 24 V
DC
Support Protocol ASCII command
LED Indicators
5-digit (ADAM-4011D)
Analog Input
Channels 1
Input Impedance
Voltage: 2 MΩ
Current: 125 Ω
(Added by users)
Input Type
T/C, mV, V or mA
Input Range
±15 mV, ±50 mV, ±100 mV,
±500 mV, ±1 V,
±2.5 V, ±20 mA
Accuracy Voltage mode: ±0.1% or
better
Current mode: ±0.2% or
better
T/C Type and Temperature Range
J
0 ~ 760° C
R
500 ~1750° C
K
0 ~ 1370° C
S
500 ~1750° C
T
-100 ~ 400° C
B
500 ~1800° C
E
0 ~ 1000° C
Span Drift ±25 ppm/° C
Zero Drift ±6 μV/° C
Wire Burnout Detector ADAM-4011D only
Digital Input
Channels 1
Logic level 0: 1 V max.
Logic level 1: 3.5 ~ 30 V
Pull up current: 0.5 mA,
10 k
Ω resistor to +5 V
Event Counter
Max. input freq: 50 Hz
Digital Output
Channels 2, open collector to
30 V, 30 mA max. load
Power Dissipation 300 mW
ADAM-4011/4011D
Common Specifications
General
Power Input Unregulated 10~30 V
DC
Connectors 1 x Plug-in terminal
blcok (#14 ~ 22 AWG)
Watchdog Timer System (1.6 second)
Analog Input
Resolution 16-bit
Sampling Rate 10 sample/second
CMR @ 50/60 Hz 150 dB
NMR @ 50/60 Hz 100 dB
Isolation Voltage 3000 V
DC
Environment
Humidity 5 ~ 95% RH
Operating Temperature -10~70° C (14~158° F)
Storage Temperature -25~85°C (-13~185°F)
Ordering Information
ADAM-4011 1-ch Thermocouple Input
Module
ADAM-4011D ADAM-4011 with
7-segment LED Display
ADAM-4012 1-ch Analog Input Module
ADAM-4013 1-ch RTD Input Module
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com